Range

SIZE Un (V) In (A) REFERENCE
WITHOUT INDICATOR

WITH INDICATOR

10x38 500V 0,5 420000 -
1 420001 -
2 420002 420102
4 420004 420104
6 420006 420106
8 420008 420108
10 420010 420110
12 420012 420112
16 420016 420116
20 420020 420120
25 420025 420125
400V 32 420032 420132

Technical data

Rated voltage 500V +10%
400V +10%
Rated currents 0,5A...32A
Rated breaking capacity 120kA
Operating class gG
Rated frequency 42…62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C
10,3 38 8,5

Weight  8gr

t-I characteristics

Cut-off characteristics

Power dissipationI2t Values

RATED CURRENT
(A)
REFERENCE * POWER DISSIPATION
(W)
PREARCING I2t
(A2s)
I2t 500V
(A2s)
I2t 400V
(A2s)
0,5 420000 1,43 4,0 10,4 8,6
1 420001 2,77 6,5 15,7 13,2
2 420002 0,60 7,0 17,6 14,6
4 420004 0,70 45 108 90
6 420006 0,80 70 166 140
8 420008 0,85 80 188 158
10 420010 1,00 120 297 248
12 420012 1,30 180 431 362
16 420016 1,90 270 636 536
20 420020 2,00 500 1162 981
25 420025 2,50 800 2034 1688
32 420032 2,90 1200 2871 2412
* Same data for INDICATOR range.

Compatible

PMX 10x38 fuse holder
U 690V AC
750V DC
In 32A

Other sizes

U 400V 690V
500V
400V
690V
500V
IN 0,5A...20A 1A...25A (690V)
32A | 40A (500V)
50A (400V)
2A...63A (690V)
80A...125A (500V)
Breaking capacity 20kA 80kA (690V)
120kA (500V/400V)
80kA (690V)
120kA (500V)

Privacy Preference Center