HORUS® photovoltaic fuse links
HORUS® cylindrical and NH fuse links are designed to protect photovoltaic strings, arrays and inverter circuits against overloads and short circuits.
On the DC side, our HORUS® photovoltaic fuse links protect against overloads and short circuits. Choose cylindrical gPV fuse links for PV strings and arrays. For sub-arrays and inverter DC inputs, the 1000 V DC NH and 1500 V DC NH XL ranges offer knife-blade and bolted connections. For 800 V AC inverter outputs, choose NH gG for general-purpose protection or NH gS for semiconductor protection. The 10×85 mm cylindrical gS fuse link protects semiconductor circuits at 1000 V AC/DC. Find matching holders and bases in the HORUS photovoltaic range.
Five cylindrical sizes cover different combinations of DC voltage and current. The 10×38 mm range starts at 1 A. The 22×65 mm range extends to 60 A at 1500 V DC. In the 14×51 and 10×85 mm sizes, the rated voltage changes with the current rating.
| Main function |
|---|
| Full-range DC overcurrent protection |
| Typical applications |
|---|
| PV arrays and string circuits |
| Range |
|---|
| 10×38 mm gPV 14×51 mm gPV 10×85 mm gPV 10/14×85 mm gPV 22×65 mm gPV |


The NH1, NH2 and NH3 sizes are rated at 1000 V DC. The 1500 V DC range uses NH1 XL, NH2 XL and NH3 L. Knife-blade versions fit the corresponding NH bases, while bolted versions mount on the busbar.
| Main function |
|---|
| Full-range DC overcurrent protection |
| Typical applications |
|---|
| PV sub-arrays, arrays and inverter DC inputs |
| Range |
|---|
| NH gPV at 1000 V DC NH XL gPV at 1500 V DC NH3 L bolted version with striker |
For the 800 V AC output, gG fuse links provide general-purpose protection and gS fuse links protect circuits containing semiconductors. A separate cylindrical gS range covers semiconductor applications at 1000 V AC/DC.
| Main function |
|---|
| Overload and short-circuit protection |
| Typical applications |
|---|
| 800 V AC inverter outputs and semiconductor circuits |
| Range |
|---|
| NH gG at 800 V AC NH gS at 800 V AC 10×85 mm gS at 1000 V AC/DC |
Which fuse link fits the circuit?
Match the protection class and voltage to your circuit, then compare current ratings and breaking capacities. A current range gives the lowest and highest ratings available in that size. Select a product name for individual ratings, connection options and order references.
Comparison table
Cylindrical gPV fuse links
Scroll the table horizontally to compare all sizes.
![]() |
![]() |
![]() |
![]() |
![]() |
|
| Feature | 10×38 mm | 14×51 mm | 10×85 mm | 10/14×85 mm | 22×65 mm |
|---|---|---|---|---|---|
| Protection Type | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) |
| Typical Application | PV strings and arrays | PV strings and arrays | PV strings and arrays | PV strings and arrays | PV strings and arrays |
| Typical Use Case | String fuse in a 10×38 PMX PV holder | 20 A string fuse at 1100 V DC | 16 A string fuse at 1500 V DC | 32 A fuse in a PMLe holder at 1500 V DC | 60 A array fuse in a 22×65 PMX PV holder |
| Rated Voltage | 1000 V DC | 1100 V DC at 15 or 20 A 1000 V DC at 25 or 32 A |
1500 V DC at 2–16 A 1200 V DC at 20 or 25 A |
1500 V DC | 1500 V DC |
| Rated Current | 1–20 A | 15, 20, 25 or 32 A | 2–25 A | 20, 25, 30 or 32 A | 40, 45, 50, 55 or 60 A |
| Breaking Capacity | 30 kA | 10 kA at 1100 V DC 30 kA at 1000 V DC |
30 kA at 1500 V DC 10 kA at 1200 V DC |
30 kA | 30 kA |
| Size | Compact | Medium | Slim, long body | Long, stepped profile | Large diameter |
| Inrush Handling1 | Lowest ≈5.5× (20 A) |
Lowest ≈6× (20 A) |
Lower ≈7.5× (20 A) |
Lowest ≈6.5× (20 A) |
Lower ≈8.5× (50 A) |
1Inrush handling at 100 ms
- Lowest <7×
- Lower 7× to <9×
- Intermediate 9× to <11×
- Higher 11× to <13×
- Highest ≥13×
For the 14×51 mm fuse, 6× (20 A) means melting begins at about 120 A. Multiples are rounded to the nearest 0.5×. Allow a margin below the curve for the expected pulse.
Comparison table
NH gPV fuse links
Scroll the table horizontally to compare all sizes.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|
| Feature | NH1 | NH2 | NH3 | NH1 XL | NH2 XL | NH3 L | NH3 L with striker |
|---|---|---|---|---|---|---|---|
| Protection Type | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) | Overload and short-circuit protection (gPV) |
| Typical Application | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs | PV sub-arrays, arrays and inverter DC inputs |
| Typical Use Case | 63 A fuse on a sub-array feeder | 250 A fuse bolted to a DC busbar | 400 A fuse on an inverter DC input | 125 A fuse on a 1500 V sub-array feeder | 250 A fuse on an array feeder | 315 A knife-blade fuse on an inverter DC input | Remote fuse indication with a 357020 microswitch |
| Rated Voltage | 1000 V DC | 1000 V DC | 1000 V DC | 1500 V DC | 1500 V DC | 1500 V DC | 1500 V DC |
| Rated Current | 25–200 A | 200 or 250 A | 200–400 A | 40–200 A | 200 or 250 A | 315–400 A | 160–500 A |
| Breaking Capacity | 30 kA | 30 kA | 30 kA | IEC 100 kA at 40–160 A, 30 kA at 200 A UL 30 kA |
IEC 100 kA UL 30 kA |
IEC 100 kA UL 30 kA |
50 kA |
| Size | Narrow body | Medium-width body | Wide body | Narrow, extended body | Medium-width, extended body | Wide, extended body | Wide, extended body |
| Inrush Handling1 | Intermediate ≈10× (200 A) |
Intermediate ≈10× (200 A) |
Intermediate ≈10× (200 A) |
Intermediate ≈10.5× (200 A) |
Intermediate ≈10.5× (200 A) |
Higher ≈11× (315 A) |
Highest ≈13.5× (315 A) |
1Inrush handling at 100 ms
- Lowest <7×
- Lower 7× to <9×
- Intermediate 9× to <11×
- Higher 11× to <13×
- Highest ≥13×
For the 1000 V DC NH1 fuse, 10× (200 A) means melting begins at about 2000 A. Multiples are rounded to the nearest 0.5×. Allow a margin below the curve for the expected pulse.
Comparison table
Inverter outputs and semiconductor circuits
Scroll the table horizontally to compare all sizes.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|
| Feature | NHC1 gG | NH1 gG | NH3 gG | NH00 gS | NH1 gS | NH3 gS | 10×85 mm gS |
|---|---|---|---|---|---|---|---|
| Protection Type | Overload and short-circuit protection (gG) | Overload and short-circuit protection (gG) | Overload and short-circuit protection (gG) | Overload and short-circuit protection (gS) | Overload and short-circuit protection (gS) | Overload and short-circuit protection (gS) | Overload and short-circuit protection (gS) |
| Typical Application | General protection on inverter AC outputs | General protection on inverter AC outputs | General protection on inverter AC outputs | Semiconductor protection on inverter AC outputs | Semiconductor protection on inverter AC outputs | Semiconductor protection on inverter AC outputs | Power electronics on AC or DC |
| Typical Use Case | 63 A fuse on an inverter output | Protection of a 690 V AC capacitor bank | 315 A fuse on an 800 V AC feeder | 63 A gS fuse on an inverter output | 160 A gS fuse on an inverter output | 355 A gS fuse on an inverter output | Semiconductor protection in a rectifier or converter |
| Rated Voltage | 800 V AC | 800 V AC | 800 V AC | 800 V AC | 800 V AC | 800 V AC | 1000 V AC/DC |
| Rated Current | 25–63 A | 80–200 A | 200–400 A | 25–100 A | 100–200 A | 250–400 A | 1–20 A |
| Breaking Capacity | 80 kA | 80 kA | 80 kA | 120 kA | 120 kA | 120 kA | 30 kA AC 10 kA DC |
| Size | Compact, narrow body | Standard, narrow body | Wide body | Short, compact body | Standard, narrow body | Wide body | Slim, long body |
| Inrush Handling1 | Intermediate ≈9× (50 A) |
Highest ≈15.5× (160 A) |
Highest ≈16× (315 A) |
Lower ≈7.5× (50 A) |
Intermediate ≈9.5× (160 A) |
Higher ≈11× (315 A) |
Lower ≈8.5× (20 A) |
1Inrush handling at 100 ms
- Lowest <7×
- Lower 7× to <9×
- Intermediate 9× to <11×
- Higher 11× to <13×
- Highest ≥13×
For the 10×85 mm gS fuse, 8.5× (20 A) means melting begins at about 170 A on the 1000 V AC curve. Multiples are rounded to the nearest 0.5×. Allow a margin below the curve for the expected pulse.
Applications of HORUS photovoltaic fuse links
The fuse protecting a PV string carries the current from that string. Where several strings feed a sub-array or an inverter input, the combined current can call for a larger fuse. The AC output has its own protection requirements.
01
PV strings
A cylindrical gPV fuse link provides overload and short-circuit protection in PV string circuits. In the 10×38 mm format, the available ratings run from 1 to 20 A at 1000 V DC.
02
PV sub-arrays
An NH gPV fuse link can protect the common feeder from a group of PV strings. At 1000 V DC, NH1 covers 25–200 A and NH2 is available at 200 A or 250 A.
03
Inverter DC inputs
For a 1500 V DC input, the extended NH sizes cover different current ranges. NH1 XL starts at 40 A. NH3 L reaches 500 A in the bolted version with striker.
04
Busbar connections
Bolted NH gPV versions connect directly to the busbar. Where the design uses a fuse base, select the knife-blade version in the matching NH size and voltage range.
05
Inverter AC outputs
At 800 V AC, NH gG fuse links provide general-purpose protection with a rated breaking capacity of 80 kA. NH gS fuse links for semiconductor protection have a rated breaking capacity of 120 kA.
06
Semiconductor circuits
The cylindrical 10×85 mm gS range covers 1–20 A at 1000 V AC/DC. Its rated breaking capacity is 30 kA on AC and 10 kA on DC.
Why choose HORUS photovoltaic fuse links?
Fuse links of the same size or current rating can have different voltage ratings and breaking capacities. Our data sheets give the electrical ratings, time-current curves and order references for each version.
01
Voltage by current rating
The rated voltage can change within one fuse size. For example, a 14×51 mm gPV fuse link rated at 20 A operates at up to 1100 V DC. The 25 A version is rated at 1000 V DC.
02
Time-current curves
Use the time-current curve for your fuse class and current rating to see how long a given current takes to melt the fuse element.
03
Power dissipation data
For a 22×65 mm gPV fuse, compare its power loss at 70% or 100% of rated current with the power the holder can dissipate at the intended load.
04
Defined breaking capacities
For NH1 XL, the IEC breaking capacity is 100 kA at 40–160 A and 30 kA at 200 A. The UL breaking capacity is 30 kA across this range.
05
Remote indication
Use microswitch 357020 with the bolted NH3 L gPV fuse link to signal fuse operation remotely. The striker actuates the switch when the fuse operates.
06
Standards by fuse class
IEC/EN 60269-6 covers gPV fuse links for photovoltaic systems. For our 800 V AC NH fuse links, IEC/EN 60269-2 applies to gG and IEC/EN 60269-4 to gS.
Need to know
What does gPV mean?
gPV is the full-range fuse category for solar photovoltaic systems in IEC 60269-6. It covers overloads and short circuits on the DC side of the installation.
Which 10×85 mm gPV ratings are suitable for 1500 V DC?
For 1500 V DC, choose a 10×85 mm gPV fuse link rated from 2 to 16 A. These versions have a breaking capacity of 30 kA. The 20 A and 25 A versions are rated at 1200 V DC and 10 kA.
Does a 10×85 mm gS fuse link have the same rating as a 10×85 mm gPV?
The 10×85 mm gS is a 1000 V AC/DC semiconductor fuse link. The 10×85 mm gPV is a photovoltaic DC fuse link with voltage ratings that vary by current. Check the class, voltage and breaking capacity as well as the physical size.
Which NH gPV fuse links are available at 1000 V DC?
The 1000 V DC range comprises NH1 at 25–200 A, NH2 at 200 or 250 A and NH3 at 200–400 A. All three sizes have a rated breaking capacity of 30 kA.
Which NH3 L version reaches 500 A?
The bolted NH3 L with striker covers 160–500 A at 1500 V DC and has a rated breaking capacity of 50 kA. The NH3 L without striker covers 315–400 A.
How can fuse operation be signalled remotely?
The bolted NH3 L version with striker accepts the 357020 microswitch. NH knife-blade versions with a compatible top indicator use the indicator microswitch. Check the indicator type before selecting the accessory.
What sizes are available for 800 V AC inverter outputs?
The NH gG range includes NHC1, NH1 and NH3. The NH gS range includes NH00, NH1 and NH3. The current ratings for a given size depend on the fuse class.
How does ambient temperature affect selection?
Above 25 °C, apply the derating factor for your cylindrical gPV fuse link. At the intended load, check that the holder can dissipate the heat from the fuse.
Where can I find the order reference?
Select the fuse size in the comparison table, then find the order reference for your current rating and, where applicable, the contact type. The bolted NH3 L with striker has its own reference series.