Range

SIZE Un (V AC) In (A) REFERENCE
NH1 800V 80 385240
100 385245
125 385250
160 385255
200 385260

Technical data

Rated voltage 800V AC +10%
Rated currents 80A...200A
Rated breaking capacity 80 kA
Operating class gG
Rated frequency 42Hz...62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1 Fuse links – general requirements
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C D E F G H I J K L
68 62 71,5 135 20 10 9,5 6 39 40 52 64

Weight  380gr

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER DISSIPATION
(W)
PREARCING I2t
(A2s)
OPERATING I2t
(A2s 800V ~)
80 385240 10,0 16550 33855
100 385245 12,0 32430 66355
125 385250 14,0 59730 122215
160 385255 18,0 95300 195000
200 385260 23,5 108000 256350

Compatible

NH1 ST 800V AC fuse base
U 690V | 800V AC
In 250 A

Other sizes

U 800V AC 800V AC
IN 25A...63A 200A...400A
Breaking capacity 80kA 80kA