NEW
REF 405015 / 405016 / 405017 / 405018 / 405118 / 405118 / 405019 / 405119 / 405020 / 455120 / 405120 / 405021 / 405121 / 405022 / 405122 / 405023 / 405123 / 405024 / 405124 / 405025 / 405125 / 14×51 gBat / 14×51 gBat Cylindrical fuse link / PMX 14×51 fuse holder / BAC 14×51 Open fuse base
SIZE | Un (V DC) | In (A) | REFERENCE | |
---|---|---|---|---|
WITHOUT INDICATOR |
WITH STRIKER |
|||
14x51 | 600V L/R ≤ 3ms |
2 | 405015 | - |
4 | 405016 | - | ||
6 | 405017 | - | ||
8 | 405018 | 405118 | ||
10 | 405019 | 405119 | ||
12 | 405020 | 405120 | ||
16 | 405021 | 405121 | ||
20 | 405022 | 405122 | ||
25 | 405023 | 405123 | ||
32 | 405024 | 405124 | ||
40 | 405025 | 405125 |
Operating class | gBat |
Rated voltage | 600V DC L/R ≤ 3ms |
Rated current | 2A...40A |
Rated breaking capacity | 50kA |
Maximum altitude * | 2000m |
Storage temperature | -40°C ... 90°C |
Operating temperature ** | -40°C ... 80°C |
* For altitudes higher than 2000m it is necessary to apply a derating in maximum current (consult us). ** For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. |
IEC/EN 60269-1
IEC/EN 60269-7
RoHS Compliant
RATED CURRENT (A) |
REFERENCE | POWER LOSS 0,8·In (W) |
POWER LOSS In (W) |
PREARCING I2t 2s) |
OPERATING I2t at Un (A2s) |
---|---|---|---|---|---|
2 | 405015 | 0,67 | 1,2 | 0,2 | 1,3 |
4 | 405016 | 0,73 | 1,3 | 2,4 | 16 |
6 | 405017 | 0,85 | 1,5 | 9 | 57 |
8 | 405018 | 0,9 | 1,6 | 5,1 | 48 |
10 | 405019 | 1,1 | 2 | 7,3 | 69 |
12 | 405020 | 1,2 | 2,2 | 13 | 112 |
16 | 405021 | 1,5 | 2,7 | 19,5 | 122 |
20 | 405022 | 1,7 | 3,1 | 38 | 210 |
25 | 405023 | 2,1 | 3,8 | 63 | 345 |
32 | 405024 | 2,2 | 4 | 153 | 835 |
40 | 405025 | 3 | 5,3 | 253 | 1380 |
PMX 14x51 fuse holder | BAC 14×51 Open fuse base | |
U | 690V AC 750V DC |
690V AC |
In | 50A | 50A |
We use cookies from third party services for a better user experience. If you continue browsing you are giving your consent for the acceptance of our Cookies Policy.