Range

SIZE Un (V AC) In (A) REFERENCE
NH00 690V 50 384050
63 384055
80 384060
100 384065
500V 125 383070
160 383075

Technical data

Rated voltage 690V AC +5%
500V AC +10%
Rated currents 50A...160A
Rated breaking capacity 80kA (690V)
120kA (500V)
Utilization category aM
Rated frequency 42...62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C D E F G H I J K L
49 44 52 78,5 15 10 9,5 6 29 35 47 59

Weight  180gr

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER DISSIPATION
(W)
PREARCING I2t
≈ 4 ms (A2s)
TOTAL I2t 400V
(A2s)
TOTAL I2t 500V
(A2s)
TOTAL I2t 690V
(A2s)
50 384050 2,4 9000 18820 22632 32130
63 384055 3,2 16300 33697 40405 57050
80 384060 4,3 19600 40519 48586 68600
100 384065 5,2 36000 74423 89239 126000
125 384070 6,7 53000 99787 116890 157872
160 384075 9,0 82000 154388 180848 244255

Other sizes

U 690V 500V
690V
500V
690V
500V
690V
500V
690V
500V
690V
IN 6A...40A 6A...200A 63A...250A 125A...400A 315A...630A 400A...1250A
Breaking capacity 80kA 80kA
120kA
80kA
120kA
80kA
120kA
80kA
120kA
80kA
120kA

Privacy Preference Center