Range

VOLTAGES POWER REFERENCE
IP00
IP23
TRT30
REVERSIBLE


230-400V 0,5kVA 70N0005000 70C0005000
1kVA 70N0010000 70C0010000
2kVA 70N0020000 70C0020000
3kVA 70N0030000 70C0030000
5kVA 70N0050000 70C0050000
8kVA 70N0080000 70C0080000
10kVA 70N0100000 70C0100000
12,5kVA 70N0125000 70C0125000
16kVA 70N0160000 70C0160000
20kVA 70N0200000 70C0200000
25kVA 70N0250000 70C0250000
31,5kVA 70N0315000 70C0315000
40kVA 70N0400000 70C0400000
50kVA 70N0500000 70C0500000
63kVA 70N0630000 70C0630000
80kVA 70N0800000 70C0800000
100kVA 70N1000000 70C1000000
125kVA 70N1250000 70C1250000
160kVA 70N1600000 70C1600000
200kVA 70N2000000 70C2000000
OTHER CHARACTERISTICS ON REQUEST SUBJECT TO AVAILABILITY AND POSSIBILITY

Technical data

Use Reversible autotransformer.
Indoor use. Dry type.
For stationary installation.
Continuous operation (ED100%).
Rated voltages 230-400V
Rated power range 0,5kVA to 200kVA
0,5kVA to 3kVA: IEC/EN61558-13
5kVA to 200kVA: IEC60076-11
Vector group YN0 connection
(star with accessible neutral)
Protection against electric shock Class I
Thermal class ≤ 25kVA: B (130°C)
≥ 31,5kVA: H (180°C)
Rated ambient temperature 40ºC
Protection index IP00 | IP23
Frequency 50/60Hz
Dielectric strength > 3kV
Ambient temperature of service * -20°C ... 70°C
Storage temperature -40°C ... 85°C
Cooling Natural air cooling
If the transformer is placed into a cabinet, it must have adequate ventilation.
* For ambient temperatures higher than 40ºC it is necessary to apply a derating.

Non short circuit proof. The user must install the appropriate protection devices (see data sheet).

Standards

IEC/EN 61558-1 Transformers, general specifications
IEC/EN 61558-2-13 Autotransformers for general use
IEC60076-11 Dry type power transformers
RoHS Compliant

Constructive characteristics

Copper windings Class F (155°C) or H (180°C)
Reinforced insulation
Flexible insulating materials Class B (130°C) or H (180°C)
Impregnation Class H (180°C)
Connection with terminal blocks protected against accidental contacts up to 63 kVA and screws for terminals for powers from 80kVA up to 200kVA.
With eyebolts for rated power from 20kVA.
Metallic case with index protection IP23 painted with epoxy in RAL7032 colour

Dimensions

IP00

POWER DIMENSIONS WEIGHT
kVA A B C D E F kg
0,5 180 85 210 140 55 6 5,5
1 180 85 210 140 55 6 6,5
2 180 95 210 140 65 6 9,1
3 240 110 260 200 75 6 16
5 240 120 260 200 85 6 18
8 240 145 261 200 110 6 27
10 300 135 311 200 95 6 31
12,5 300 145 311 200 105 6 40
16 300 165 316 200 125 6 44
20 360 170 366 300 115 8 56
25 360 180 366 300 125 8 68
31,5 420 200 425 300 140 8 86
40 420 210 425 300 150 8 100
50 480 225 500 400 155 10 107
63 480 240 500 400 175 10 135
80 480 280 510 400 195 10 160
100 480 300 510 400 215 10 180
125 600 320 600 500 180 16 240
160 600 340 600 500 200 16 270
200 600 350 530 500 220 16 325
These dimensions belongs to autotransformers with rated voltage of 230-400V.
For another voltages the dimensions can be very different.

IP23

POWER DIMENSIONS WEIGHT
kVA A B C 1 D E F kg
0,5 235 240 285 140 215 12 9,0
1 235 240 285 140 215 12 9,5
2 235 240 285 140 215 12 12
3 285 290 335 200 265 12 20
5 285 290 335 200 265 12 22,5
8 285 290 335 200 265 12 31
10 375 300 435 200 270 12 38
12,5 375 300 435 200 270 12 47
16 375 300 435 200 270 12 51
20 450 400 480 300 370 12 66
25 450 400 480 300 370 12 78
31,5 510 400 540 300 370 12 97
40 510 400 540 300 370 12 111
50 540 500 610 400 470 12 126
63 540 500 610 400 470 12 156
80 540 500 610 400 470 12 180
100 540 500 610 400 470 12 197
160 880 530 830 500 500 12 300
200 880 730 830 500 500 12 365
These dimensions belongs to autotransformers with rated voltage of 230-400V.
For another voltages the dimensions can be very different.

1 Eyebolts ≥ 20kVA +45mm

Other versions

POWER 1...125kVA
VOLTAGES 230-400V

Privacy Preference Center