Sizes

NEW
U 1500V DC 1500V DC 1500V DC 1500V DC
IN 40A...200A 200A | 250A 315A...400A 160A...500A
Breaking capacity 30kA (UL)
100kA (IEC)*
30kA (UL)
100kA (IEC)
30kA (UL)
100kA (IEC)
50kA
Certifications
* IEC Breaking capacity: 40A...160A ➔ 100kA | 200A ➔ 30kA

Range

SIZE Un (V DC) BLADE In (A) REFERENCE
NH1 XL 1500V
KNIFE BLADE
40 372225
50 372230
63 372235
80 372240
100 372245
125 372250
160 372255
200 372260

BOLTED BLADE
40 372225 B
50 372230 B
63 372235 B
80 372240 B
100 372245 B
125 372250 B
160 372255 B
200 372260 B
NH2 XL 1500V
KNIFE BLADE
200 372350
250 372360

BOLTED BLADE
200 372350 B
250 372360 B
NH3 L 1500V
KNIFE BLADE
315 372445
350 372448
355 372450
400 372455

BOLTED BLADE
315 372445 B
350 372448 B
355 372450 B
400 372455 B
NH3 L
BOLTED BLADE WITH STRIKER
1500V 160 372420P
200 372425P
250 372435P
315 372445P
355 372450P
400 372455P
450 372463P
500 372465P

Technical data

Operating class gPV
Minimum interrupt rating 1,35·In
Non fusing current 1,13·In
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1 Fuse links – general requirements
IEC/EN 60269-6 Fuse links for solar photovoltaic systems
UL248-1 Fuse links – general requirements
UL248-19 Photovoltaic fuse links
RoHS Compliant