REF 370070 / 370075 / NH00 ST 690V
SIZE | Un (V DC) | In (A) | REFERENCE |
NH00 | 440V L/R ≤ 10ms |
125 | 370070 |
160 | 370075 |
Rated voltage | 440V DC L/R ≤ 10ms |
Rated currents | 125A | 160A |
Rated breaking capacity | 30kA |
Operating class | gBat |
Storage temperature | -40°C ... 90°C |
Operating temperature * | -40°C ... 80°C |
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. |
IEC/EN 60269-1
IEC 60269-7
RoHS Compliant
RATED CURRENT (A) |
REFERENCE | POWER LOSS 0,8·In (W) |
POWER LOSS In (W) |
PREARCING I2t 2s) |
OPERATING I2t at Un (A2s) |
---|---|---|---|---|---|
125 | 370070 | 8,3 | 14,7 | 6850 | 8800 |
160 | 370075 | 10,5 | 18,2 | 12900 | 16500 |
NH00 ST 690V/800V fuse base | |||
U | 690V 800V |
||
In | 160 A | ||
We use cookies from third party services for a better user experience. If you continue browsing you are giving your consent for the acceptance of our Cookies Policy.