RAPIDPLUS semiconductor fuse links
RAPIDPLUS semiconductor fuse links are high-speed protective devices for power electronics. gS and gR ranges clear overloads and short circuits; aR ranges provide short-circuit protection.
DF Electric’s RAPIDPLUS family combines cylindrical, NH and square-body fuse links for semiconductor protection in power rectifiers, UPS systems, converters, motor drives, soft starters, solid-state relays, photovoltaic inverters and welding equipment. The family includes gS and gR full-range fuse links for overload and short-circuit protection, plus aR fuse links for short-circuit protection of power semiconductor devices. Available ratings extend from compact 10 × 38 and 10 × 85 cylindrical formats to NH and SQB fuse links for higher current applications. Electrical maxima do not apply to every fuse link. Select the protection class and format first, then verify rated voltage, current, breaking capacity, I²t, power dissipation, dimensions, temperature derating, connection and coordination in the technical data for the chosen reference. Explore the seven ranges below and compare the published ratings that define their intended use.
The compact 10 × 85 gS range provides full-range protection at 1000 V AC/DC. Ratings from 1 to 20 A combine high-speed operation with low let-through energy. Published breaking capacities are 30 kA AC and 10 kA DC.
| Main function |
|---|
| Protection against overloads and short circuits |
| Typical applications |
|---|
| Power electronics and renewable-energy systems up to 1000 V AC/DC |
| Range |
|---|
| 10 × 85 gS 1000 V AC/DC |
Cylindrical gR fuse links provide full-range protection in 10 × 38, 14 × 51 and 22 × 58 mm sizes. The range covers 1 to 100 A at 690 V AC +5% and is also rated at 440 V DC. Selected 14 × 51 and 22 × 58 ratings are available with a striker.
| Main function |
|---|
| Protection against overloads and short circuits |
| Typical applications |
|---|
| Semiconductors, cables and switchgear in compact power-electronics assemblies |
| Range |
|---|
| 10 × 38 gR 14 × 51 gR 22 × 58 gR |
Cylindrical aR fuse links provide short-circuit protection for semiconductors with low I²t and reduced arc voltage. The 10 × 38, 14 × 51 and 22 × 58 mm sizes cover 1 to 100 A at 690 V AC and 700 V DC. Selected ratings are available with a striker.
| Main function |
|---|
| Short-circuit protection for power semiconductor devices |
| Typical applications |
|---|
| High-speed semiconductor protection coordinated with overload protection |
| Range |
|---|
| 10 × 38 aR 14 × 51 aR 22 × 58 aR |
The NH gS 690 V AC range provides full-range protection from 20 to 630 A in NH000, NH00, NH1, NH2 and NH3 sizes. Published DC ratings are 440 V for NH000 and NH00, and 550 V for NH1, NH2 and NH3. Breaking capacity is 100 kA AC and 30 kA DC.
| Main function |
|---|
| Protection against overloads and short circuits |
| Typical applications |
|---|
| Power conversion equipment requiring NH full-range semiconductor protection |
| Range |
|---|
| NH000 gS 690 V AC NH00 gS 690 V AC NH1 gS 690 V AC NH2 gS 690 V AC NH3 gS 690 V AC |
The NH gS 800 V AC range provides full-range protection from 25 to 400 A in NH00, NH1 and NH3 sizes. Its reduced power dissipation supports use with a range of fuse bases and fuse-switch disconnectors. Rated breaking capacity is 120 kA.
| Main function |
|---|
| Protection against overloads and short circuits |
| Typical applications |
|---|
| High-voltage AC power conversion in standard NH assemblies |
| Range |
|---|
| NH00 gS 800 V AC NH1 gS 800 V AC NH3 gS 800 V AC |
NH aR fuse links provide short-circuit protection from 16 to 1000 A in NH000, NH1, NH2 and NH3 sizes. The range is rated at 690 V AC; published DC ratings are 440 V for NH000 and 550 V for NH1, NH2 and NH3. A trip indicator can provide visual or microswitch signalling.
RAPIDPLUS SQB aR fuse links provide short-circuit protection from 80 to 1400 A at 690 V AC. SQB1, SQB2 and SQB3 sizes are available with flush-end, 80 mm blade and 110 mm blade contacts. Rated breaking capacity is 120 kA.
What is the difference between gS, gR and aR semiconductor fuse links?
gS and gR fuse links provide full-range protection against overloads and short circuits. aR fuse links provide short-circuit protection for power semiconductor devices and require coordinated overload protection. Choose the class together with the required voltage, current, format, breaking capacity, I²t and installation conditions.
Comparison table
DF Electric RAPIDPLUS semiconductor fuse links
Compare the published family-level ratings, then consult the selected reference for complete technical data.
Cylindrical ranges
![]() |
|||
| Feature | 10 × 85 gS | Cylindrical gR | Cylindrical aR |
|---|---|---|---|
| Protection type | Overloads and short circuits | Overloads and short circuits | Short circuits |
| Rated voltage | 1000 V AC/DC | 690 V AC +5% 440 V DC |
690 V AC 700 V DC |
| Rated current | 1–20 A | 1–100 A | 1–100 A |
| Breaking capacity | 30 kA AC 10 kA DC |
200 kA AC 30 kA DC |
200 kA AC 30 kA DC |
| Sizes / versions | 10 × 85 | 10 × 38 14 × 51 22 × 58 |
10 × 38 14 × 51 22 × 58 |
| Striker option | — | 14 × 51 8, 10, 12, 16, 20, 25, 32, 40, 50 A 22 × 58 20, 25, 32, 40, 50, 63, 80, 100 A |
14 × 51 8, 10, 12, 16, 20, 25, 32, 40, 50 A 22 × 58 20, 25, 32, 40, 50, 63, 80, 100 A |
NH and square-body ranges
![]() |
||||
| Feature | NH gS 690 V AC |
NH gS 800 V AC |
NH aR | SQB aR |
|---|---|---|---|---|
| Protection type | Overloads and short circuits | Overloads and short circuits | Short circuits | Short circuits |
| Rated voltage | 690 V AC +10% 440/550 V DC1 |
800 V AC +10% | 690 V AC +10% 440/550 V DC2 |
690 V AC |
| Rated current | 20–630 A | 25–400 A | 16–1000 A | 80–1400 A |
| Breaking capacity | 100 kA AC 30 kA DC |
120 kA | 120 kA AC 30 kA DC |
120 kA |
| Sizes / versions | NH000 NH00 NH1 NH2 NH3 |
NH00 NH1 NH3 |
NH000 NH1 NH2 NH3 |
SQB1 SQB2 SQB3 |
| Connection / indication | NH blade contacts | NH blade contacts | NH blade contacts Trip indicator Optional microswitch |
Flush end contacts 80 mm blade contacts 110 mm blade contacts |
1 NH gS 690 V AC. NH000 and NH00 are rated at 440 V DC; NH1, NH2 and NH3 at 550 V DC.
2 NH aR. NH000 is rated at 440 V DC; NH1, NH2 and NH3 at 550 V DC.
Ratings are family-level summaries. Check the technical data, time-current curves, I²t, power dissipation, dimensions, temperature derating, connection requirements and coordination for the selected reference.
Applications of semiconductor fuse links
RAPIDPLUS fuse links protect power semiconductor devices and associated circuits across industrial and renewable-energy power conversion. The suitability of a specific reference depends on the protection class, electrical ratings, fault conditions and installation requirements.
01
Power rectifiers and converters
High-speed fuse links limit current and let-through energy during faults in rectifiers and industrial converters. Select the protection class and I²t required by the semiconductor devices and circuit.
02
UPS and critical power systems
RAPIDPLUS ranges support semiconductor protection in UPS equipment and critical power conversion. Coordination must account for operating current, prospective fault current and continuity requirements.
03
Motor drives and soft starters
Semiconductor fuse links protect diodes, thyristors, triacs and IGBTs used in AC and DC motor drives and soft starters. Selection must allow normal operating conditions while clearing the specified faults.
04
Photovoltaic inverters
The range includes options for power semiconductor protection in photovoltaic inverters. The 10 × 85 gS fuse link provides a compact 1000 V AC/DC option; suitability still depends on the actual circuit and coordination study.
05
Solid-state relays
Fast fault clearing and low let-through energy support protection of semiconductor switching devices used in solid-state relays. Verify current rating, I²t and overload coordination for the specific assembly.
06
Welding inverters
RAPIDPLUS fuse links can protect power semiconductor devices in welding inverters. Correct selection considers the duty cycle, fault level, thermal conditions and protection required by the semiconductor manufacturer.
Why choose DF Electric RAPIDPLUS semiconductor fuse links
RAPIDPLUS combines high-speed semiconductor protection with cylindrical, NH and square-body formats. Seven published ranges cover different protection classes, voltages, currents, breaking capacities and connection requirements, supported by reference-specific technical data.
01
High-speed current limitation
The ranges are designed for rapid fault clearing, low I²t and controlled let-through energy to reduce thermal and electrodynamic stress on sensitive power semiconductor devices.
02
gS, gR and aR classes
Full-range gS and gR options clear overloads and short circuits. Partial-range aR options focus on semiconductor short-circuit protection and are coordinated with overload protection.
03
Three fuse-link formats
Cylindrical, NH and square-body formats provide compact through high-current options. Available dimensions, contacts and indication features depend on the selected range.
04
Broad electrical coverage
Published options extend from 1 A cylindrical ratings to 1400 A SQB ratings, with AC and DC voltage capabilities defined by range. Maxima are not interchangeable between versions.
05
High breaking capacities
Published breaking capacities reach 200 kA AC in the cylindrical gR and aR ranges. The applicable value must be checked at the specified voltage and for the selected reference.
06
Reference-specific documentation
Product pages and data sheets provide ratings, dimensions, characteristic curves, I²t and power-dissipation data. Published ranges reference IEC/EN 60269-1 and IEC/EN 60269-4.