Range

SIZE Un (V DC) In (A) REFERENCE
WITHOUT INDICATOR

WITH STRIKER

22x58 600V
L/R ≤ 3ms
40 405041 405141
50 405042 405142
63 405043 405143
80 405044 405144

Technical data

Utilization category gBat
Rated voltage 600V DC
L/R ≤ 3ms
Rated current 40A...80A
Rated breaking capacity 50kA
Maximum altitude * 2000m
Storage temperature -40°C ... 90°C
Operating temperature ** -40°C ... 80°C
* For altitudes higher than 2000m it is necessary to apply a derating in maximum current (consult us).
** For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1
IEC/EN 60269-7
RoHS Compliant

Dimensions

A B C D E
22,2 58 15,5 8 3,7

Weight  50gr

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER LOSS 0,8·In
(W)
POWER LOSS In
(W)
PREARCING I2t
2s)
OPERATING I2t at Un
(A2s)
2 405041 3,1 5,4 330 1400
4 405042 3,8 6,8 590 2500
6 405043 4,3 7,7 1050 4440
8 405044 4,9 8,7 2360 9990

Compatible

PMX 22x58 fuse holder BAC 22x58 Open fuse base
U 690V AC
750V DC
690V AC
In 50A 50A

Other sizes

U 600V DC
IN 2A...40A
Breaking capacity 50kA