REF 368445 / 368450 / 368455 / NH3 L fuse base 1500V DC
SIZE | Un (V DC) | In (A) | REFERENCE |
NH3 L | 1500V L/R ≤ 3ms |
315 | 368445 |
355 | 368450 | ||
400 | 368455 |
Operating class | gBat |
Rated voltage | 1500V DC L/R ≤ 3ms |
Rated current | 315A...400A |
Rated breaking capacity | 100kA |
Storage temperature | -40°C ... 90°C |
Operating temperature * | -40°C ... 80°C |
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. |
IEC/EN 60269-1
IEC 60269-7
RoHS Compliant
RATED CURRENT (A) |
REFERENCE | POWER LOSS 0,8·In (W) |
POWER LOSS In (W) |
PREARCING I2t 2s) |
OPERATING I2t at Un (A2s) |
---|---|---|---|---|---|
315 | 368445 | 34,8 | 61 | 114000 | 172080 |
355 | 368450 | 38,8 | 68 | 159230 | 240350 |
400 | 368455 | 42,8 | 75 | 212000 | 320000 |
NH3 L 1500V DC fuse base | |
U | 1500V DC |
In | 200 A |