SIZE | Un (V AC) | In (A) | REFERENCE |
NH00 | 500V | 125 | 381070 |
160 | 381075 |
Rated voltage | 500V AC +10% |
Rated currents | 125A | 160A |
Rated breaking capacity | 120kA |
Operating class | gG |
Rated frequency | 42...62Hz |
Storage temperature | -40°C ... 90°C |
Operating temperature * | -40°C ... 80°C |
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. |
IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant
RATED CURRENT (A) |
REFERENCE | POWER DISSIPATION (W) |
PREARCING I2t ≈ 4 ms (A2s) |
TOTAL I2t 230V (A2s) |
TOTAL I2t 400V (A2s) |
TOTAL I2t 500V (A2s) |
---|---|---|---|---|---|---|
125 | 381070 | 9,0 | 40500 | 70900 | 107301 | 136895 |
160 | 381075 | 10,3 | 78400 | 137000 | 207711 | 265000 |
NH00 ST 690V/800V fuse base | Microswitch for NH fuse links | NH ST 1000V AC/DC Fuse puller | |
U | 690V 800V |
250V AC | 1000V DC |
In | 160 A | 5 A | |