RAPIDPLUS gR Cylindrical fuse links are capable to clearing all types of overcurrents, overloads as well as short-circuits, thus the fuse links protect semiconductors as well as cables and all switchgear of installation.
RAPIDPLUS gR range comprise three sizes with dimensions 10×38, 14×51 and 22×58, with rated currents between 1A and 100A and a rated voltage of 690V AC. Sizes 14×51 and 22×58 are available also with striker, for use in fuse bases with microswitch.
UL certification according to UL248 standard. UL file Nr. E477155.
| SIZE | Un (V AC) | In (A) | REFERENCE | |
|---|---|---|---|---|
WITHOUT STRIKER![]() |
WITH STRIKER![]() |
|||
| 10x38 | 690V | 1 | 492000 | - |
| 2 | 492001 ![]() |
- | ||
| 3 | 492002 ![]() |
- | ||
| 4 | 492003 ![]() |
- | ||
| 6 | 492004 ![]() |
- | ||
| 8 | 492005 ![]() |
- | ||
| 10 | 492006 ![]() |
- | ||
| 12 | 492007 ![]() |
- | ||
| 16 | 492008 ![]() |
- | ||
| 20 | 492009 ![]() |
- | ||
| 25 | 492010 ![]() |
- | ||
| 32 | 492011 ![]() |
- | ||
| 14x51 | 690V | 4 | 492014 ![]() |
- |
| 6 | 492015 ![]() |
- | ||
| 8 | 492016 ![]() |
492116 ![]() |
||
| 10 | 492017 ![]() |
492117 ![]() |
||
| 12 | 492018 ![]() |
492118 ![]() |
||
| 16 | 492019 ![]() |
492119 ![]() |
||
| 20 | 492020 ![]() |
492120 ![]() |
||
| 25 | 492021 ![]() |
492121 ![]() |
||
| 32 | 492022 ![]() |
492122 ![]() |
||
| 40 | 492023 ![]() |
492123 ![]() |
||
| 50 | 492024 ![]() |
492124 ![]() |
||
| 22x58 | 690V | 20 | 492033 ![]() |
492133 ![]() |
| 25 | 492034 ![]() |
492134 ![]() |
||
| 32 | 492035 ![]() |
492135 ![]() |
||
| 40 | 492036 ![]() |
492136 ![]() |
||
| 50 | 492037 ![]() |
492137 ![]() |
||
| 63 | 492038 ![]() |
492138 ![]() |
||
| 80 | 492039 ![]() |
492139 ![]() |
||
| 100 | 492040 ![]() |
492140 ![]() |
||
| Operating class | gR |
| Rated voltage | 690V AC (UL/IEC) 440V DC (L/R=10ms)(IEC) |
| Rated breaking capacity | 200kA @690V AC 30kA @440V AC |
| Storage temperature | -40°C ... 90°C |
| Operating temperature * | -40°C ... 80°C |
| * For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. | |
IEC/EN 60269-1
IEC/EN 60269-4
UL248-1
UL248-13
RoHS Compliant
We use cookies from third party services for a better user experience. If you continue browsing you are giving your consent for the acceptance of our Cookies Policy.