Range

SIZE Un (V AC) In (A) REFERENCE
NH00 400V 125 380070
160 380075

Technical data

Rated voltage 400V AC +10%
Rated currents 125A | 160A
Rated breaking capacity 120kA
Operating class gG
Rated frequency 42...62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C D E F G H I J K L
49 44 52 78,5 15 10 9,5 6 29 35 47 59

Weight  180gr

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER DISSIPATION
(W)
PREARCING I2t
(A2s)
TOTAL I2t 230V
(A2s)
TOTAL I2t 400V
(A2s)
125 380070 7,2 49300 78300 110300
160 380075 9,5 85000 134980 190000

Other sizes

U 400V 400V 400V 400V
IN 10A...100A 50A...250A 100A...400A 315A...630A
Breaking capacity 120kA 120kA 120kA 120kA