NEW
REF 494001 / 494002 / 494003 / 494004 / 494005 / 494006 / 494008 / 494010 / 494012 / 494016 / 494020
| SIZE | Un (V AC/DC) | In (A) | REFERENCE |
|---|---|---|---|
| 10x85 | 1000V | 1 | 494001 |
| 2 | 494002 | ||
| 3 | 494003 | ||
| 4 | 494004 | ||
| 5 | 494005 | ||
| 6 | 494006 | ||
| 8 | 494008 | ||
| 10 | 494010 | ||
| 12 | 494012 | ||
| 16 | 494016 | ||
| 20 | 494020 |
| Rated voltage | 1000V AC/DC |
| Rated currents | 1A...20A |
| Rated breaking capacity | 30kA AC 10kA DC |
| Operating class | gS |
| Rated frequency | 42...62Hz |
| Storage temperature | -40°C ... 90°C |
| Operating temperature * | -40°C ... 80°C |
| * For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. | |
IEC/EN 60269-1 Fuse links – general requirements
IEC/EN 60269-4 Fuse links for semiconductors protection
RoHS Compliant
| RATED CURRENT (A) |
REFERENCE | POWER DISSIPATION (W @ In) |
POWER DISSIPATION (W @ 0,8·In) |
PREARCING I2t (A2s) |
I2t 1000V (A2s) |
|---|---|---|---|---|---|
| 1 | 494001 | 0,75 | 0,45 | 0,2 | 0,42 |
| 2 | 494002 | 1 | 0,6 | 2 | 4,4 |
| 3 | 494003 | 1,1 | 0,65 | 14 | 19 |
| 4 | 494004 | 1,2 | 0,7 | 41 | 56 |
| 5 | 494005 | 1,3 | 0,77 | 80 | 107 |
| 6 | 494006 | 1,5 | 0,89 | 12 | 44 |
| 8 | 494008 | 1,6 | 0,93 | 46 | 176 |
| 10 | 494010 | 1,7 | 1 | 74 | 240 |
| 12 | 494012 | 1,8 | 1,06 | 145 | 470 |
| 16 | 494016 | 3,1 | 1,82 | 190 | 615 |
| 20 | 494020 | 3,3 | 1,95 | 415 | 1380 |
![]() |
|
| PMLe PV fuse holder | |
| U | 1000V AC | 1500V DC |
| In | 32 A |
We use cookies from third party services for a better user experience. If you continue browsing you are giving your consent for the acceptance of our Cookies Policy.