Three-phase reactors
Three-phase line or motor reactors for power converters (intended for the attenuation of notches and spikes as well as reduction of harmonics and limitation of inrush currents in power converters and motor drives). There are also types for the protection of capacitor banks in power factor correction equipment with presence of harmonics (to avoid resonance effects, to minimize harmonic currents through the capacitors and to reduce losses, increasing capacitor life. Manufactured with electrical steel with low losses and copper windings. On request we can manufacture reactors with other characteristics, with built-in thermal switch, etc.
MODELS
LINE REACTOR
Three-phase reactors intended for the attenuation of notches and spikes, reduction of harmonics and limitation of inrush currents in converters and variable speed drives. Drop voltage of 4% of the rated voltage (400V). Manufactured with electrical steel with low losses and copper windings. On request we can manufacture reactors with other characteristics or with thermal switch.
NATURAL AIR COOLING
OTHER CHARACTERISTICS ON REQUEST
VOLTAGE DROP
4% at IN (400V)
THERMAL CLASS
B
MAX AMBIENT TEMPERATURE
40ºC
FREQUENCY
50Hz
CLASS
I
PROTECTION INDEX
IP00
DIELECTRIC STRENGTH PRI-SEC
> 4kV
STANDARDS
IEC/EN 61558
IEC 60076
HARMONIC CIRCUIT FILTER REACTOR
Three-phase reactors for the protection of capacitor banks in power factor correction equipment with presence of harmonics. Avoids resonance effects, minimizes harmonic currents through the capacitors and reduces the losses, increasing capacitor life. Manufactured with electrical steel with low losses and copper windings. Built-in thermal switch. On request we can manufacture reactors with other characteristics.
THERMAL MICROSWITCH
OTHER CHARACTERISTICS ON REQUEST
VOLTAGE DROP
400V
FILTERING FACTOR
P=0,07 (7%)
fr
189Hz
TOLERANCE L
3%
LINEARITY (95% IN)
1,8·IN
MAX PERMANENT OVERLOAD
1,17 · IN
THERMAL CLASS
B
MAX AMBIENT TEMPERATURE
40ºC
FREQUENCY
50Hz
CLASS
I
PROTECTION INDEX
IP00
DIELECTRIC STRENGTH PRI-SEC
> 4kV
STANDARDS
IEC/EN 61558
IEC/EN 60289
RATED CURRENT
On request we can manufacture reactors with other characteristics or with thermal switch.